Jinan Amrta Air Conditioning Co.,Ltd
Home Product Low Ambient Temperature Air Source Heat Pump Unit

Low Ambient Temperature Air Source Heat Pump Unit

Available in: Heating

Capacity: 10kW~20kW

Refrigerant: R410A/R134A/R407C

Application: Low temperature ambient

Amrta’s AC range of chillers with the EVIcycle increase the maximum temperature difference remarkably and provide a COP up to 4.5, which makes the hot water
system much more efficient. They can be widely used in the commercial situation.

 

High efficient

The application of EVI technology together with the high efficiency heat exchanger improves the heat exchanging rate.

 

Low working temperature

Units achieve optimum performance at ambient temperature as low as -25oC, ensuring 60oC hot water all year round.

 

Easy control

Intelligent control system with the Carel controller makes it much easier to control your unit whenever you need.

 

EVI technology

The EVI compressor ensures the unit operate safely at low ambient temperature with higher efficiency and less noise.

Item                      Model ASHP-10L ASHP-15L ASHP-20L
DB/WB In/Out water Capacity Unit
7oC/6oC 36oC/41oC Heating kW 9.6 14.5 19.1
Power input kW 2.5 3.8 5.1
50oC/60oC Heating kW 9.8 14.5 19.8
Power input kW 3.3 4.8 6.5
-12oC/-14oC 36oC/41oC Heating kW 6.1 9.2 11.8
Power input kW 2.32 3.7 4.7
50oC/60oC Heating kW 6.6 9.8 12.8
Power input kW 3.2 4.8 6.4
-20oC/-oC 36oC/41oC Heating kW 5.2 7.7 10.3
Power input kW 2.3 3.6 4.6
50oC/55oC Heating kW 5.4 8.1 10.8
Power input kW 2.9 4.3 5.8
-25oC/-oC 36oC/41oC Heating kW 4.5 6 8.9
Power input kW 2.4 3.4 4.8
50oC/55oC Heating kW 4.7 6.8 9.5
Power input kW 2.9 4.5 5.9
35oC/— 12oC/7oC Cooling kW 7.2 10.2 14.2
Power input kW 2.7 3.7 5.2
Compressor Type   Scroll Scroll Scroll
Brand   Copeland Copeland Copeland
Qty   1 1 1
Control methods   Electronic expansion valve
Condensing fan Type   Axial, plastic fan blade Axial, plastic fan blade Axial, plastic fan blade
Qty   1 2 2
Power input w 90 90 90
Max power input kW 4.1 5.8 8.2
Max working current A 18 29 36
Pipe size R1’’ R1’’ R1’’
Evaporator type   High efficiency tank type heat exchanger
Water flow Cooling ( △ 5k) m3/h 1.24 1.75 2.4
Heating ( △ 5k/ △ 10k) m3/h 1.58/0.79 2.49/1.25 2.9/1.45
Water resistance kPa 40 45 46
Refrigerant Type   R410A
Charge amount kg 3.6 5.3 6.1
Working range oC -25oC-46oC
Power supply 1N~220V 50Hz
Dimension mm 1200x560x858 1000x560x1316 1100x620x1316
Noise level dB(A) 54 56 56
Weight kg 122 150 170

Note: Without water pump and expansion tank, but with paddle flow switch.

                                 